Water expands when heated; in a closed circuit, that expansion needs somewhere to go. The expansion tank is where the system breathes without triggering the safety valve.

Volume2 – 5,000 liters
Pre-charge0.5 – 4 bar (adjustable)
Operating temperature−10 °C … +100 °C
MembraneEPDM · butyl · food-grade
Request a volume calculation
GAS 2 – 5000 liters PN 6 – PN 16

Membrane closed expansion tank · gas cushion and water volume

Why it's needed

What happens without an expansion tank?

When the tank is wrongly sized, the system doesn't stop right away; it gets by for months and then causes problems in unexpected places.

Prevents the safety valve from opening needlessly

When an undersized tank fills up, pressure rises and the safety valve discharges water. As the system cools, pressure drops and water gets topped up again. Every cycle brings fresh oxygen into the circuit.

Prevents corrosion from the start

Continuous water top-up means continuously carrying dissolved oxygen into a closed circuit. The basic condition for protecting a closed circuit from corrosion is keeping the same water in the loop.

Pre-charge is the system's most critical setting

The pre-charge pressure on the tank's gas side is set relative to static pressure. A tank with the wrong setting won't do its job even at the correct volume — it either never engages, or stays full from the start.

Dampens pressure fluctuation

Pressure keeps changing through heating and cooling cycles. The tank smooths out that variation, putting less strain on fittings and gasket surfaces.

The membrane separates water from gas

In the membrane type, the water never contacts the nitrogen cushion. This way the gas doesn't dissolve into the water, and the tank itself doesn't turn into a source of air in the circuit.

Volume is determined by calculation, not guesswork

System water volume, maximum operating temperature, pre-charge pressure and the safety valve's set pressure all go into the calculation together. Change any one of the four and the result changes.

Types

Which type, for which job?

Membrane construction and intended use determine the selection.

MOST COMMON

Fixed membrane

The membrane is fixed to the body. The standard, economical solution for heating circuits.

  • Economical and common
  • For heating circuits
  • Membrane cannot be replaced
REPLACEABLE

Bladder membrane

The membrane can be removed and replaced through a flanged cover. Provides long life and easy maintenance.

  • Membrane is replaceable
  • Preferred at large volumes
  • Water only contacts the membrane
POTABLE WATER

Potable water booster tank

For domestic water and pressurization lines. Requires a food-grade membrane material.

  • Membrane suitable for drinking water
  • Used in pressurization groups
  • Reduces pump start cycles

Selection criteria

What data is volume calculated from?

Volume can't be calculated without these four data points; the rest determine type and material.

ParameterWhy it mattersWhat we need from you

System total water volume

The total water content of the boiler, pipework, radiators or fan coils, and exchangers. Expansion volume is derived directly from this.

Liters

Maximum operating temperature

Determines how much the water will expand. The difference between a 90 °C and a 60 °C regime shows up directly in volume.

°C

Pre-charge (static pressure)

The water column from the tank's elevation up to the highest point. Calculated from building height.

bar

Safety valve set pressure

The system's allowable upper limit. The gap between this and the pre-charge determines the tank's usable volume.

bar

Fluid type

A glycol mix expands differently than water, and its compatibility with the membrane material is checked separately.

Water / % glycol

Membrane material

EPDM is standard on a heating circuit. Domestic water needs a certified food-grade membrane.

EPDM / butyl / food-grade

Mounting style

Wall-hung, legged, or on a stand. At large volumes, floor load capacity should also be checked.

Wall-hung / legged

Connection size and location

The tank connects close to the pump's suction side and the boiler. An isolation valve and a drain should sit on the connection.

DN/threaded size

This much is enough for a quote

You don't need all of it. We'll work out anything missing together with you.

Create a quote request
  • System total water volume or boiler capacity
  • Temperature regime (e.g. 90/70 °C)
  • Building height or static pressure
  • Safety valve set pressure
  • Fluid type and glycol ratio
  • Heating or domestic water

FAQ

Questions from the field

The four questions we hear most often at the quote stage.

I don't know my system water volume — what should I do?

It's possible to arrive at an approximate volume based on boiler capacity and system type. Radiator heating, fan coils and underfloor heating each carry a different water volume per unit of capacity. Tell us the capacity and installation type, and we'll start from a reasonable estimate and set the safety margin accordingly.

Who sets the pre-charge pressure?

The tank ships from the factory with a standard pre-charge, and that value doesn't have to match your building. Before installation, while the tank is empty, it needs to be set on the gas side to match static pressure. If this step is skipped, the tank won't do its job even at the correct volume — this is the mistake we see most often in the field.

My tank keeps discharging water — why?

Usually one of three reasons: the volume was undersized, the pre-charge was set incorrectly, or the membrane has ruptured. Checking the membrane is simple — if water comes out of the gas valve, the membrane has failed. We tell the other two apart by calculation.

How long does an expansion tank last?

The membrane is a wear part; its life varies with operating temperature, the number of pressure cycles, and water quality. In fixed-membrane types, the whole tank is replaced once the membrane fails. In bladder-membrane types, only the membrane is replaced — at large volumes, this difference gives a clear long-term advantage.

Next step

Let's work out the volume together

Share your system volume and regime, and let's work out the tank volume and pre-charge together.